LOGO POWER SIEMENS
February 17, 2025SITOP PSU100S/1AC/24VDC/10A
February 18, 2025
LOGO!POWER 24 V / 4 A stabilized power supply input: 100-240 V AC output: 24 V DC / 4 A
Stock: 1 available
Category: POWER SUPPLY
| input | |
| type of the power supply network 1-phase AC or DC | |
| supply voltage at AC | |
| ● minimum rated value | 100 V |
| ● maximum rated value | 240 V |
| ● initial value | 85 V |
| ● full-scale value | 264 V |
| input voltage at DC | 110 … 300 V |
| wide range input | Yes |
| overvoltage overload capability | 300 V AC for 1 s |
| buffering time for rated value of the output current in the event of power failure minimum | 40 ms |
| operating condition of the mains buffering | at Vin = 187 V |
| line frequency | 50/60 Hz |
| line frequency | 47 … 63 Hz |
| input current | |
| ● at rated input voltage 120 V | 1.95 A |
| ● at rated input voltage 230 V | 0.97 A |
| current limitation of inrush current at 25 °C maximum | 31 A |
| I2t value maximum | 2.5 A²·s |
| fuse protection type | internal |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C |
| output | |
| voltage curve at output | Controlled, isolated DC voltage |
| output voltage at DC rated value | 24 V |
| output voltage | |
| ● at output 1 at DC rated value | 24 V |
| output voltage adjustable | Yes; via potentiometer |
| adjustable output voltage | 22.2 … 26.4 V |
| relative overall tolerance of the voltage | 3 % |
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1 % |
| ● on slow fluctuation of ohm loading | 0.1 % |
| residual ripple | |
| ● maximum | 200 mV |
| ● typical | 30 mV |
| voltage peak | |
| ● maximum | 300 mV |
| ● typical | 50 mV |
| display version for normal operation | Green LED for output voltage OK |
| behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
| response delay maximum | 0.5 s |
| voltage increase time of the output voltage | |
| ● typical | 100 ms |
| output current | |
| ● rated value | 4 A |
| ● rated range | 0 … 4 A; +55 … +70 °C: Derating 2%/K |
| supplied active power typical | 96 W |
| bridging of equipment | Yes |
| number of parallel-switched equipment resources for increasing the power | 2 |
| efficiency | |
| efficiency in percent | 89.1 % |
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical | 11.7 W |
| ● during no-load operation maximum | 0.3 W |