PR4184 PR ELECTRONICS
February 13, 2025711H TYCO
February 13, 2025
Universal uni-/bipolar signal transmitter
Stock: 2 available
Categories: SPLITTERS, CONVERTERS & ISOLATORS
| Environmental Conditions | |
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20…28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
| Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
| Mechanical specifications | |
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Weight approx. | 155 g |
| Weight incl. 4501 / 451x (approx.) | 170 g / 185 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2…13.2 Hz | ±1 mm |
| 13.2…100 Hz | ±0.7 g |
| Common specifications | |
| Supply | |
| Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
| Max. required power | ≤ 2.5 W |
| Max. power dissipation | ≤ 2.5 W |
| Isolation voltage | |
| Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
| Response time | |
| Response time (0…90%, 100…10%) | < 20 ms |
| Auxiliary supplies | |
| 2-wire loop supply | > 16 V / 20 mA |
| 3-wire loop supply | > 18 V / 20 mA |
| Loop supply limitation | 30 mA |
| Programming | PR 4500 communication interfaces |
| Signal / noise ratio | > 60 dB |
| Cut-off frequency (3 dB) | > 40 Hz |
| Accuracy | Better than 0.05% of selected range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
| Input specifications | |
| Current input | |
| Signal range | ±23 mA |
| Programmable measurement ranges | 0…20 and 4…20 mA ± 10 and ± 20 mA |
| Input voltage drop | 1.4 V @ 20 mA |
| Loop error detection, 4…20 mA: Low | < 3.6 mA |
| Loop error detection, 4…20 mA: High | > 21 mA |
| Voltage input | |
| Signal range | ±12 V |
| Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC ±1, ±5 and ±10 V |
| Input resistance | > 2 MΩ |
| Output specifications | |
| Current output | |
| Signal range | 0…23 mA (unipolar) -23…+23 mA (bipolar) |
| Current limit | ≤ 28 mA (unipolar) ± 28 mA (bipolar) |
| Load stability | ≤ 0.001% of span / 100 Ω |
| Response time, programmable | 0.0…60.0 s |
| Output limitation, on 4…20 and 20…4 mA signals | 3.8…20.5 mA |
| Output limitation, on other unipolar mA signals | 0 and 115% of max. value |
| Output limitation, on bipolar mA signals | ±115% of min. & max. values |
| Sensor error indication, at 4…20 mA input: selectable | Low, High, Zero, None |
| Active unipolar and bipolar mA output | |
| Programmable ranges | 0…20 and 4…20 mA ±10 and ±20 mA |
| Direct or Inverted Action | |
| V-curve function, active signals, 100-0-100% | 20-0-20 mA |
| Load (@ current output) | ≤ 800 Ω |
| Passive 2-wire mA output | |
| Programmable ranges | 0…20 and 4…20 mA Direct or Inverted action |
| V-curve function, 100-0-100% | 20-0-20 mA |
| External loop supply | 3.5 – 26 V |
| Voltage output | |
| Programmable signal ranges | 0/0.2…1; 0/1…5 ; 0/2…10 V ±1, ±5 and ±10 V |
| Direct or Inverted action | |
| V-curve function, 100-0-100% | 1-0-1, 5-0-5 and 10-0-10 V |
| Load (@ voltage output) | ≥ 500 kΩ |
| Response time, programmable | 0.0…60.0 s |
| Output limitation – outside range: on unipolar V signals starting from 0 | 0 and 115% of max. value |
| Output limitation – outside range: on unipolar V signals with offset | -5% of min. value and 115% of max. value |
| Output limitation – outside range: on bipolar V signals | ±115% of min. & max. values |
| Sensor error indication, at 4…20 mA input: selectable | Low, High, Zero, None |